M2VF2-4D-R2/N
AI

The **M2VF2-4D-R2/N** is a specific model of a **Slim-style Signal Conditioner (Isolator)** manufactured by **M-System**. Its primary function is to accept a DC voltage or current input and provide two independent, isolated DC outputs.
Below is a detailed breakdown of its electronic specifications and characteristics based on the model code.
---
## 1. Model Code Breakdown
The alphanumeric string defines the specific hardware configuration:
| Code Segment | Meaning | Specification |
|:---|:---|:---|
| **M2VF2** | Model Series | Slim-style Signal Conditioner (V-Unit Series) |
| **4D** | Input Type | 0 – 10V DC |
| **R** | Power Input | 24V DC |
| **2** | Output 1 | 4 – 20mA DC |
| **N** | Output 2 | None (Standard configuration) |
---
## 2. Key Electronic Specifications
### Input & Output Characteristics
* **Input Impedance:** Typically 1 MΩ minimum for voltage inputs.
* **Output Load Resistance:**
* Current Output (4-20mA): Max 550 Ω.
* Voltage Output: Max 1mA.
* **Response Time:** ≤ 0.5 seconds (0 – 90%).
### Power & Isolation
* **Power Consumption:** Approximately 3W.
* **Isolation Structure:** 4-way isolation (Input to Output 1 to Output 2 to Power).
* **Dielectric Strength:** 2000V AC @ 1 minute (Input to output to power to ground).
* **Insulation Resistance:** ≥ 100 MΩ with 500V DC.
### Performance
* **Accuracy:** ±0.1% of span.
* **Temperature Coefficient:** ±0.015% per °C (±0.008% per °F).
---
## 3. Physical & Installation Features
* **Construction:** Small-footprint, plug-in base structure.
* **Wiring:** M3.5 screw terminals (nickel-plated steel).
* **Housing Material:** Flame-resistant resin (color: Black).
* **Mounting:** DIN rail or surface mounting.
---
## 4. Typical Applications
This electronic part is commonly used in industrial automation for:
1. **Signal Conversion:** Changing a 0-10V sensor signal into a 4-20mA signal for long-distance transmission.
2. **Ground Loop Elimination:** Preventing electrical noise and interference between field instruments and a PLC/DCS.
3. **Signal Splitting:** Providing two isolated outputs from a single sensor input.
- ⤷
What are the wiring diagrams for the M2VF2-4D-R2/N?
- ⤷ Can the output range be recalibrated manually on this unit?
- ⤷ What is the difference between the M2VF2 and the M2VS series?