Back Button XTOG032CC1 Datasheet HTML 42Page - Eaton All Rights Reserved. XTOG032CC1 Datasheet HTML 43Page - Eaton All Rights Reserved. XTOG032CC1 Datasheet HTML 44Page - Eaton All Rights Reserved. XTOG032CC1 Datasheet HTML 45Page - Eaton All Rights Reserved. XTOG032CC1 Datasheet HTML 46Page - Eaton All Rights Reserved. XTOG032CC1 Datasheet HTML 47Page - Eaton All Rights Reserved. XTOG032CC1 Datasheet HTML 48Page - Eaton All Rights Reserved. XTOG032CC1 Datasheet HTML 49Page - Eaton All Rights Reserved. XTOG032CC1 Datasheet HTML 50Page - Eaton All Rights Reserved. Next Button
Zoom Inzoom in Zoom Outzoom out
 46 / 68 page
background image
Advanced Overload Education, continued
Description
Definition
Source
Result
Motor Insight
Protection
Load Protection
Under current or
low power
Average rms current provided to the
motor falls below normal operating
conditions.
Under current is usually associated
with a portion of the user’s load
disappearing. Examples of this would
be a broken belt, a dry-pump (low
suction head) or a dead-headed
centrifugal pump.
If under current goes undetected, a
mechanical failure can and has
occurred. In the case of a pump,
running a pump dry or running a pump
in a dead-headed condition can cause
excessive heating, damaging
expensive seals and breaking down
desired fluid properties.
Motor Insight has two protection settings
to detect this: under current and low
power. Low power is a more consistent
way of ensuring detection as power is
linear with motor load, where as current
is not. An unloaded motor may draw 50%
of its rated current, but the power draw
will be less than 10% of rated power due
to a low power factor.
High power
The motor load is drawing more power
than it should at normal operating
conditions.
This is typical of batch processing
applications where several ingredients
flow into a mixer. When a substance’s
consistency changes and viscosity
increases from what is expected, the
motor may use more power to blend
the mixture. Out-of-tolerance
conditions can be detected using the
High Power and Low Power settings.
If a high-power fault goes undetected,
the result may be a batch of material
that does not meet specification.
Monitors the three-phase real power. If
the real power value is estimated above
the set threshold for the set length of
time, a fault is detected and the overload
will trip the starter. Additionally, power
can be monitored in real-time.
Line Protection
Over voltage
When the line voltage to the motor
exceeds the specified rating.
Poor line quality.
An over voltage condition leads to a
lower than rated current draw and a
poor power factor. A trip limit of 110%
of rated voltage is recommended. Over
voltage can also lead to exceeding
insulation ratings.
Monitors the maximum rms value of
the three-phase voltages. If the rms
value rises above the set threshold for the
set length of time, a fault is detected and
the overload can trip the starter or send
and display an alarm of the condition. All
line-related faults have an “alarm-no-
trip” mode.
Under voltage
When the line voltage to the motor is
below the specified rating.
Poor line quality.
An under voltage condition leads to
excessive current draw. This increases
the heating of the motor windings and
can shorten insulation life. A trip limit
set to 90% of rated voltage is
recommended.
Monitors the minimum rms value of the
three-phase voltages. If the rms value
drops below the set threshold for the
set length of time, a fault is detected
and the overload can trip the starter or
send and display an alarm of the
condition. All line-related faults have
an “alarm-no-trip” mode.
Power-up delay
Allows for starting motors and loads
in a deliberate fashion.
When there is a power failure, or
power cycle, multiple loads come
online simultaneously.
Multiple loads starting simultaneously
can cause sags affecting the operation
of devices that may prevent successful
startup.
If power is lost to a motor driving a
pump, it may be necessary to delay a
restart to allow the pump to come to a
complete stop to prevent starting a
motor during backspin.
Configurable to delay closing the fault
relay on power-up. For each Motor Insight
controlling a motor, a different setting can
be programmed, helping to maintain the
integrity of your line power.
Features and benefits
C441 Overload and monitoring relay
47
AUTOMATION AND CONTROL
www.eaton.com/seasia-electrical
1.2
1



Html Pages

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68


Datasheet Descarga

Go To PDF Page


Enlace URL



¿ALLDATASHEET es útil para Ud.?  [ DONATE ] 

Todo acerca de Alldatasheet   |   Publicidad   |   Contáctenos   |   Política de Privacidad   |   Enlace a la hoja de datos    |   Intercambio de Enlaces   |   Lista de Fabricantes
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com