Back Button XTOG097EC1 Datasheet HTML 41Page - Eaton All Rights Reserved. XTOG097EC1 Datasheet HTML 42Page - Eaton All Rights Reserved. XTOG097EC1 Datasheet HTML 43Page - Eaton All Rights Reserved. XTOG097EC1 Datasheet HTML 44Page - Eaton All Rights Reserved. XTOG097EC1 Datasheet HTML 45Page - Eaton All Rights Reserved. XTOG097EC1 Datasheet HTML 46Page - Eaton All Rights Reserved. XTOG097EC1 Datasheet HTML 47Page - Eaton All Rights Reserved. XTOG097EC1 Datasheet HTML 48Page - Eaton All Rights Reserved. XTOG097EC1 Datasheet HTML 49Page - Eaton All Rights Reserved. Next Button
Zoom Inzoom in Zoom Outzoom out
 45 / 68 page
background image
Advanced Overload Education
Description
Definition
Source
Result
Motor Insight
Protection
Motor Protection
Thermal overload
Overload is a condition in which current
draw to a motor exceeds 115% of
the full load amperage rating over a
period of time for an inductive motor.
An increase in the load or torque that
is being driven by the motor.
A low voltage supply to the motor would
cause the current to go high to maintain
the power needed.
A poor power factor would cause
above normal current draw.
Increase in current draw. Current leads
to heat and insulation breakdown,
which can cause system failure.
Additionally, an increase in current can
increase power consumption and
waste valuable energy.
Thermal trip behavior is defined by UL,
CSA and IEC standards.
Trip class is settable from 5–30 by 1
Provides power factor monitoring and low
voltage protection features.
Jam
Jam is similar to thermal overload in
that it is a current draw on the motor
above normal operating conditions.
Mechanical stall, interference, jam or
seizure of the motor or motor load.
The motor attempts to drive the load,
which has more resistive force due to
the mechanical interference. In order to
drive the load, the motor draws an
abnormal amount of current, which can
lead to insulation breakdown and
system failure.
Provides a configurable Jam setting that
is active during “motor run state” to avoid
nuisance trips.
Trip Threshold 150–400% of FLA.
Trip Delay 1–20 seconds.
Ground fault
A line to ground fault.
A current leakage path
to ground.
An undetected ground fault can burn
through multiple insulation windings,
ultimately leading to motor failure.
Motor Insight has ground fault protection
capability down to 0.15 amps estimated
from the existing three-phase CTs using
the residual current method. That is, the
three-phase current signals should sum to
zero unless a ground fault (GF) condition
is present. In the case of a GF, Motor
Insight can alarm, trip the starter, or trip
an alternative relay that can be used to
shunt trip a breaker or light up a warning
light. GF current can also be monitored in
real-time through the advanced
monitoring capabilities.
Note: GF settable thresholds vary with
motor FLA. 0.15 amps may not be
available in all cases.
Imbalanced phases
(voltage and current)
Uneven voltage or currents between
phases in a three-phase system.
When a three-phase load is powered with
a poor quality line, the voltage per phase
may be imbalanced.
Imbalanced voltage causes large
imbalanced currents and as a result this
can lead to motor stator windings being
overloaded, causing excessive heating,
reduced motor efficiency and reduced
insulation life.
Provides two protection settings that
address this problem. The user can
choose to set current imbalance
thresholds or voltage imbalance
thresholds, each of which can trip the
starter. Additionally, both of these may
be monitored through Motor Insight’s
advanced monitoring capabilities,
allowing the customer to notice in real-
time when and where a condition is
present.
Phase loss—current
(single-phasing)
One of the three-phase current is
not present.
Multiple causes, loose wire, improper
wiring, grounded phase, open fuse,
and so on.
Single-phasing can lead to unwanted
motor vibrations in addition to the results
of imbalanced phases as listed above.
Fixed protective setting that takes the
starter offline if a phase drops below
60% of the other two phases.
Phase rotation
(phase-reversal)
Improper wiring, leading to phases being
connected to the motor improperly.
A miswired motor. Inadvertent phase-
reversal by the utility.
Phase-reversal can cause unwanted
directional rotation of a motor. In the
event that the load attached to the motor
can only be driven in one direction, the
result could be significant mechanical
failure and/or injury to an operator.
Configurable phase protection, allowing
the user to define the phase sequencing
intended for that application. If no phase
sequence is required, the user has the
ability to disable this feature.
Frequency variance
When line frequency
is inconsistent.
Malfunctioning alternator speed
regulator, or poor line quality caused by
an overload of a supply powered
by individual sources.
Variations in frequency can cause
increases in losses, decreasing the
efficiency of the motor. In addition,
this can result in interference with
synchronous devices.
Advanced monitoring capabilities
allow the user to monitor frequency
in real-time.
C441 Overload and monitoring relay
Features and benefits
AUTOMATION AND CONTROL
www.eaton.com/seasia-electrical
46
1
1
1.2



Html Pages

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68


Datasheet Descarga

Go To PDF Page


Enlace URL



¿ALLDATASHEET es útil para Ud.?  [ DONATE ] 

Todo acerca de Alldatasheet   |   Publicidad   |   Contáctenos   |   Política de Privacidad   |   Enlace a la hoja de datos    |   Intercambio de Enlaces   |   Lista de Fabricantes
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com