47 / 68 page ![]() Data Sheet ADE7953 Rev. A | Page 47 of 68 INDICATION OF POWER DIRECTION The ADE7953 includes sign indication on the active and reactive energy measurements. Sign indication allows positive and nega- tive energy to be identified and billed separately if required. It also helps detect a miswiring condition. This feature is available on both Current Channel A and Current Channel B. Power direction information is available on both a dedicated output pin (REVP) and via a set of internal registers and interrupts (see the section and the section). Reverse Power Sign Indication REVERSE POWER The REVP pin (Pin 20) on the ADE7953 provides a reverse power indicator. This pin can be configured to provide polarity information about the active or reactive power on Current Channel A or Current Channel B. The REVP output is high by default and goes low if the angle between the voltage and current input is greater than 90°. REVP is unlatched and, therefore, returns high when the reverse power condition is no longer true. Changes to the REVP output pin occur synchronously to the falling edge of the CF1 pin by default (see ). Figure 65 The measurement and channel indicated by the REVP pin are selected by the configuration of the CF output. By default, the REVP pin is configured to output synchronous to CF1 and represents the measurement selected on CF1 using the CF1SEL bits in the CFMODE register (Address 0x107). By default, this measurement is the active power on Current Channel A. If the CF1SEL bits are set to 0x0001, the REVP pin indicates the polarity of the reactive power on Current Channel A. The REVP indicator can be configured to output based on CF2 by setting the REVP_CF bit in the CONFIG register (Address 0x102). In this configura- tion, the CF2SEL bits in the CFMODE register determine the measurement represented on the REVP output. If the selected CF pin is configured to output another measurement, such as apparent power or IRMS, the REVP output is disabled. To improve the visibility of a reverse polarity condition if an LED light is used, a 1 Hz pulse mode is available on the REVP pin. In this mode, the REVP output pin is low by default and outputs a 1 Hz pulse if the reverse polarity condition is true. This pulse has a 50% duty cycle. Similar to normal mode, this mode is also unlatched, and the REVP output returns high when the reverse polarity is no longer true. To enable the REVP pulse mode, the REVP_PULSE bit in the CONFIG register (Address 0x102) should be set to 1. The REVP output pin is disabled in the corresponding no-load condition. For example, if the reverse polarity information for Current Channel A active power is present on the REVP pin and the active energy on Current Channel A is in the no-load condition, the REVP output is disabled and held in its current state. SIGN INDICATION The ADE7953 includes four sign indication bits that indicate the polarity of the active power on Current Channel A (APSIGN_A), the active power on Current Channel B (APSIGN_B), the reactive power on Current Channel A (VARSIGN_A), and the reactive power on Current Channel B (VARSIGN_B). These bits are located in the ACCMODE register (Address 0x201 and Address 0x301). All four bits are unlatched and read only. A low reading (0) on any of these bits indicates that the correspond-ing power reading is positive; a high reading (1) indicates that the corresponding power reading is negative. These bits are enabled by default and are disabled in the corresponding no-load condition. In addition to the sign indication bits, the ADE7953 also includes four sign indication interrupts. If enabled, these interrupts cause the IRQ pin to go low when the polarity of the power changes. The interrupts are triggered on both positive-to-negative and negative-to-positive polarity changes. These interrupts are dis- abled by default and can be enabled by setting the APSIGN_A and VARSIGN_A bits in the IRQENA register (Address 0x22C and Address 0x32C), and the APSIGN_B and VARSIGN_B bits in the IRQENB register (Address 0x22F and Address 0x32F). See the section. ADE7953 Interrupts Note that in absolute or positive-only accumulation mode, these bits are fixed at 0. See the Active Energy Accumulation Modes section and the Reactive Energy Accumulation Modes section. CF1 ENTER REVERSE CONDITION REVP CURRENT AND VOLTAGE INPUTS EXIT REVERSE CONDITION REVP HIGH REVP LOW Figure 65. REVP Output |
|
Enlace URL |
| ¿ALLDATASHEET es útil para Ud.? [ DONATE ] |
Todo acerca de Alldatasheet | Publicidad | Contáctenos | Política de Privacidad | Enlace a la hoja de datos | Intercambio de Enlaces | Lista de Fabricantes All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|
Family Site : ic2ic.com |
icmetro.com |