Motor de Búsqueda de Datasheet de Componentes Electrónicos
  Mexican  ▼
ALLDATASHEET.COM.MX

X  

3UG3501 Datasheet(PDF) 15 Page - List of Unclassifed Manufacturers

No. de pieza 3UG3501
Descripción Electrónicos  Monitoring and Control Devices
PDF  114 Pages
Scroll/Zoom Zoom In 100%  Zoom Out
Fabricante Electrónico  ETC2 [List of Unclassifed Manufacturers]
Página de inicio  
Logo ETC2 - List of Unclassifed Manufacturers

3UG3501 Datasheet(HTML) 15 Page - List of Unclassifed Manufacturers

Back Button 3UG3501 Datasheet HTML 11Page - List of Unclassifed Manufacturers 3UG3501 Datasheet HTML 12Page - List of Unclassifed Manufacturers 3UG3501 Datasheet HTML 13Page - List of Unclassifed Manufacturers 3UG3501 Datasheet HTML 14Page - List of Unclassifed Manufacturers 3UG3501 Datasheet HTML 15Page - List of Unclassifed Manufacturers 3UG3501 Datasheet HTML 16Page - List of Unclassifed Manufacturers 3UG3501 Datasheet HTML 17Page - List of Unclassifed Manufacturers 3UG3501 Datasheet HTML 18Page - List of Unclassifed Manufacturers 3UG3501 Datasheet HTML 19Page - List of Unclassifed Manufacturers Next Button
Zoom Inzoom in Zoom Outzoom out
 15 / 114 page
background image
SIMOCODE 3UF Motor Management and Control Devices
7/15
Siemens LV 1 T · 2006
SIMOCODE pro 3UF7
motor management and control devices
Basic units
Control circuit
Rated control supply voltage Us (acc. to EN 61131-2)
110 ... 240 V AC/DC; 50/60 Hz
24 V DC
Operating range
0.85 ... 1.1 x Us
0.8 ... 1.2 × Us
Power input
• Basic unit 1 (3UF7 000)
7VA
5W
• Basic unit 2 (3UF7 010)
incl. two expansion modules connected to basic unit 2
10 VA
7W
Rated insulation voltage Ui
V
300 (at pollution degree 3)
Rated impulse withstand voltage Uimp
kV
4
Relay outputs
•Number
3 monostable relay outputs
• Auxiliary contacts of the 3 relay outputs
Floating NO contact (NC contact response can be parameterized with
internal signal conditioning), 2 relay outputs are jointly and 1 relay output is
separately connected to a common potential; they can be freely assigned to
the control functions (e.g. for line, wye and delta contactors and for signaling
the operating status)
• Specified short-circuit protection for auxiliary contacts
(relay outputs)
• Fuse links, operational class gL/gA 6 A, quick 10 A (IEC 60947-5-1)
• Miniature circuit-breaker 1.6 A, C characteristic (IEC 60947-5-1)
• Miniature circuit-breaker 6 A, C characteristic (Ik < 500 A)
• Rated uninterrupted current
A
6
• Rated short-circuit capacity
AC-15
6A/24V AC
6A/120 V AC
3A/230 V AC
DC-13
2 A/24 V DC
0.55 A/60 V DC
0.25 A/125 V DC
Inputs (binary)
4 inputs supplied internally by the device electronics with 24 V DC and
connected to a common potential for acquiring process signals
(e.g. local control station, key switch, limit switch, ...),
freely assignable to control functions
Thermistor motor protection (binary PTC)
• Summation cold resistance
k
W
ˆ 1.5
•Operating value
k
W
3.4 ... 3.8
• Return value
k
W
1.5 ... 1.65
Conductor cross-sections
• Tightening torque
Nm
0.8 ... 1.2
• Solid
mm2
1 × (0.5 ... 4.0); 2 × (0.5 ... 2.5)
• Finely stranded with end sleeve
mm2
1 × (0.5 ... 2.5); 2 × (0.5 ... 1.5)
• AWG cable (solid)
AWG
1xAWG20 to12/2xAWG20 to14
• AWG cable (finely stranded)
AWG
1xAWG20 to14/2xAWG20 to16
Current measuring modules or
current/voltage measuring modules
Mounting
• Set current Ie = 0.3 ... 3 A; 2.4 ... 25 A; 10 ... 100 A
(3UF7 1.0, 3UF7 1.1, 3UF7 1.2)
Snap-on mounting onto 35 mm standard mounting rail or
screw fixing with additional push-in lugs
• Set current Ie = 20 ... 200 A (3UF7 103, 3UF7 113)
Snap-on mounting onto 35 mm standard mounting rail,
screwing onto mounting plate or direct fixing on contactor
• Set current Ie = 63 ... 630 A (3UF7 104, 3UF7 114)
Screw fixing onto mounting plate or direct fixing on contactor
System interfaces
for connection to a basic unit
Main circuit
3UF7 1.0
3UF7 1.1
3UF7 1.2
3UF7 1.3
3UF7 1.4
Set current Ie
A
0.3 ... 3
2.4 ... 25
10 ... 100
20 ... 200
63 ... 630
Rated insulation voltage Ui
(with pollution degree 3)
V
690
1000
Rated impulse withstand voltage Uimp
kV
6
8
Rated frequency
Hz
50/60
Type of current
Three-phase current
Short-circuit
Additional short-circuit protection is required in main circuit1)
Accuracy of current measurement (in the range 1 x minimum
set current Iu to 8 x max. set current Io)
%
–3
Typical voltage measuring ranges
• Phase-to-phase voltage/line-to-line voltage (e.g. UL1 L2)V
110 ... 690
• Phase voltage (e.g. UL1)V
65 ... 400
Accuracy
• Of voltage measurement
(phase voltage UL in the range 230 ... 400 V)
%
–3 (typical)
• Of power factor measurement
%
–5 (typical)
• Of apparent power measurement
%
–5 (typical)
Notes on voltage measurement
• Grounded network
suitable for three-phase supply with grounded neutral point
• Rated control supply voltage Us
grounded mass or neutral conductor is required



Html Pages

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100  ...More


Datasheet Descarga

Go To PDF Page


Enlace URL



¿ALLDATASHEET es útil para Ud.?  [ DONATE ] 

Todo acerca de Alldatasheet   |   Publicidad   |   Contáctenos   |   Política de Privacidad   |   Enlace a la hoja de datos    |   Intercambio de Enlaces   |   Lista de Fabricantes
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com